Network Working Group J. Case, Editor Request for Comments: 1628 SNMP Research, Incorporated Category: Standards Track May 1994

                UPS Management Information Base

Status of this Memo

This document specifies an Internet standards track protocol for the Internet community, and requests discussion and suggestions for improvements. Please refer to the current edition of the "Internet Official Protocol Standards" (STD 1) for the standardization state and status of this protocol. Distribution of this memo is unlimited.

Introduction

This memo defines a portion of the Management Information Base (MIB) for use with network management protocols in the Internet community. In particular, it defines objects for managing uninterruptible power supply (UPS) systems.

The SNMPv2 Network Management Framework

The SNMPv2 Network Management Framework consists of four major components. They are:

  o    RFC 1442 which defines the SMI, the mechanisms used for
       describing and naming objects for the purpose of management.
  o    STD 17, RFC 1213 defines MIB-II, the core set of managed
       objects for the Internet suite of protocols.
  o    RFC 1445 which defines the administrative and other
       architectural aspects of the framework.
  o    RFC 1448 which defines the protocol used for network access
       to managed objects.

The Framework permits new objects to be defined for the purpose of experimentation and evaluation.

Object Definitions

Managed objects are accessed via a virtual information store, termed the Management Information Base or MIB. Objects in the MIB are defined using the subset of Abstract Syntax Notation One (ASN.1) defined in the SMI. In particular, each object type is named by an OBJECT IDENTIFIER, an administratively assigned name. The object type together with an object instance serves to uniquely identify a specific instantiation of the object. For human convenience, we often use a textual string, termed the descriptor, to refer to the object type.

Overview

This document defines the managed objects for Uninterruptible Power Supplies which are to be manageable via the Simple Network Management Protocol (SNMP).

Definitions

UPS-MIB DEFINITIONS ::= BEGIN

IMPORTS

   MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
   OBJECT-IDENTITY, Counter32, Gauge32, Integer32
       FROM SNMPv2-SMI
   DisplayString, TimeStamp, TimeInterval, TestAndIncr,
     AutonomousType
       FROM SNMPv2-TC
   MODULE-COMPLIANCE, OBJECT-GROUP
       FROM SNMPv2-CONF;

upsMIB MODULE-IDENTITY

   LAST-UPDATED "9402230000Z"
   ORGANIZATION "IETF UPS MIB Working Group"
   CONTACT-INFO
          "        Jeffrey D. Case
            Postal: SNMP Research, Incorporated
                    3001 Kimberlin Heights Road
                    Knoxville, TN  37920
                    US
               Tel: +1 615 573 1434
               Fax: +1 615 573 9197
            E-mail: [email protected]"
   DESCRIPTION
           "The MIB module to describe Uninterruptible Power
           Supplies."
   ::= { mib-2 33 }

PositiveInteger ::= TEXTUAL-CONVENTION

   DISPLAY-HINT "d"
   STATUS       current
   DESCRIPTION
           "This data type is a non-zero and non-negative value."
   SYNTAX       INTEGER (1..2147483647)

NonNegativeInteger ::= TEXTUAL-CONVENTION

   DISPLAY-HINT "d"
   STATUS       current
   DESCRIPTION
           "This data type is a non-negative value."
   SYNTAX       INTEGER (0..2147483647)

upsObjects OBJECT IDENTIFIER ::= { upsMIB 1 }

-- -- The Device Identification group. -- All objects in this group except for upsIdentName and -- upsIdentAttachedDevices are set at device initialization -- and remain static. --

upsIdent OBJECT IDENTIFIER ::= { upsObjects 1 }

upsIdentManufacturer OBJECT-TYPE

   SYNTAX     DisplayString (SIZE (0..31))
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The name of the UPS manufacturer."
   ::= { upsIdent 1 }

upsIdentModel OBJECT-TYPE

   SYNTAX     DisplayString (SIZE (0..63))
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The UPS Model designation."
   ::= { upsIdent 2 }

upsIdentUPSSoftwareVersion OBJECT-TYPE

   SYNTAX     DisplayString (SIZE (0..63))
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The UPS firmware/software version(s).  This variable
           may or may not have the same value as
           upsIdentAgentSoftwareVersion in some implementations."
   ::= { upsIdent 3 }

upsIdentAgentSoftwareVersion OBJECT-TYPE

   SYNTAX     DisplayString (SIZE (0..63))
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The UPS agent software version.  This variable may or
           may not have the same value as
           upsIdentUPSSoftwareVersion in some implementations."
   ::= { upsIdent 4 }

upsIdentName OBJECT-TYPE

   SYNTAX     DisplayString (SIZE(0..63))
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "A string identifying the UPS.  This object should be
           set by the administrator."
   ::= { upsIdent 5 }

upsIdentAttachedDevices OBJECT-TYPE

   SYNTAX     DisplayString (SIZE(0..63))
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "A string identifying the devices attached to the
           output(s) of the UPS.  This object should be set by
           the administrator."
   ::= { upsIdent 6 }

-- -- Battery Group --

upsBattery OBJECT IDENTIFIER ::= { upsObjects 2 }

upsBatteryStatus OBJECT-TYPE

   SYNTAX     INTEGER {
       unknown(1),
       batteryNormal(2),
       batteryLow(3),
       batteryDepleted(4)
   }
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The indication of the capacity remaining in the UPS
           system's batteries.   A value of batteryNormal
           indicates that the remaining run-time is greater than
           upsConfigLowBattTime.  A value of batteryLow indicates
           that the remaining battery run-time is less than or
           equal to upsConfigLowBattTime.  A value of
           batteryDepleted indicates that the UPS will be unable
           to sustain the present load when and if the utility
           power is lost (including the possibility that the
           utility power is currently absent and the UPS is
           unable to sustain the output)."
   ::= { upsBattery 1 }

upsSecondsOnBattery OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "seconds"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "If the unit is on battery power, the elapsed time
           since the UPS last switched to battery power, or the
           time since the network management subsystem was last
           restarted, whichever is less.  Zero shall be returned
           if the unit is not on battery power."
   ::= { upsBattery 2 }

upsEstimatedMinutesRemaining OBJECT-TYPE

   SYNTAX     PositiveInteger
   UNITS      "minutes"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "An estimate of the time to battery charge depletion
           under the present load conditions if the utility power
           is off and remains off, or if it were to be lost and
           remain off."
   ::= { upsBattery 3 }

upsEstimatedChargeRemaining OBJECT-TYPE

   SYNTAX     INTEGER (0..100)
   UNITS      "percent"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "An estimate of the battery charge remaining expressed
           as a percent of full charge."
   ::= { upsBattery 4 }

upsBatteryVoltage OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "0.1 Volt DC"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The magnitude of the present battery voltage."
   ::= { upsBattery 5 }

upsBatteryCurrent OBJECT-TYPE

   SYNTAX     Integer32
   UNITS      "0.1 Amp DC"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The present battery current."
   ::= { upsBattery 6 }

upsBatteryTemperature OBJECT-TYPE

   SYNTAX     Integer32
   UNITS      "degrees Centigrade"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The ambient temperature at or near the UPS Battery
           casing."
   ::= { upsBattery 7 }

-- -- Input Group --

upsInput OBJECT IDENTIFIER ::= { upsObjects 3 }

upsInputLineBads OBJECT-TYPE

   SYNTAX     Counter32
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "A count of the number of times the input entered an
           out-of-tolerance condition as defined by the
           manufacturer.  This count is incremented by one each
           time the input transitions from zero out-of-tolerance
           lines to one or more input lines out-of-tolerance."
   ::= { upsInput 1 }

upsInputNumLines OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The number of input lines utilized in this device.
           This variable indicates the number of rows in the
           input table."
   ::= { upsInput 2 }

upsInputTable OBJECT-TYPE

   SYNTAX     SEQUENCE OF UpsInputEntry
   MAX-ACCESS not-accessible
   STATUS     current
   DESCRIPTION
           "A list of input table entries.  The number of entries
           is given by the value of upsInputNumLines."
   ::= { upsInput 3 }

upsInputEntry OBJECT-TYPE

   SYNTAX     UpsInputEntry
   MAX-ACCESS not-accessible
   STATUS     current
   DESCRIPTION
           "An entry containing information applicable to a
           particular input line."
   INDEX { upsInputLineIndex }
   ::= { upsInputTable 1 }

UpsInputEntry ::= SEQUENCE {

   upsInputLineIndex   PositiveInteger,
   upsInputFrequency   NonNegativeInteger,
   upsInputVoltage     NonNegativeInteger,
   upsInputCurrent     NonNegativeInteger,
   upsInputTruePower   NonNegativeInteger

}

upsInputLineIndex OBJECT-TYPE

   SYNTAX     PositiveInteger
   MAX-ACCESS not-accessible
   STATUS     current
   DESCRIPTION
           "The input line identifier."
   ::= { upsInputEntry 1 }

upsInputFrequency OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "0.1 Hertz"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The present input frequency."
   ::= { upsInputEntry 2 }

upsInputVoltage OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "RMS Volts"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The magnitude of the present input voltage."
   ::= { upsInputEntry 3 }

upsInputCurrent OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "0.1 RMS Amp"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The magnitude of the present input current."
   ::= { upsInputEntry 4 }

upsInputTruePower OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "Watts"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The magnitude of the present input true power."
   ::= { upsInputEntry 5 }

-- -- The Output group. --

upsOutput OBJECT IDENTIFIER ::= { upsObjects 4 }

upsOutputSource OBJECT-TYPE

   SYNTAX     INTEGER {
       other(1),
       none(2),
       normal(3),
       bypass(4),
       battery(5),
       booster(6),
       reducer(7)
   }
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The present source of output power.  The enumeration
           none(2) indicates that there is no source of output
           power (and therefore no output power), for example,
           the system has opened the output breaker."
   ::= { upsOutput 1 }

upsOutputFrequency OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "0.1 Hertz"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The present output frequency."
   ::= { upsOutput 2 }

upsOutputNumLines OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The number of output lines utilized in this device.
           This variable indicates the number of rows in the
           output table."
   ::= { upsOutput 3 }

upsOutputTable OBJECT-TYPE

   SYNTAX     SEQUENCE OF UpsOutputEntry
   MAX-ACCESS not-accessible
   STATUS     current
   DESCRIPTION
           "A list of output table entries.  The number of
           entries is given by the value of upsOutputNumLines."
   ::= { upsOutput 4 }

upsOutputEntry OBJECT-TYPE

   SYNTAX     UpsOutputEntry
   MAX-ACCESS not-accessible
   STATUS     current
   DESCRIPTION
           "An entry containing information applicable to a
           particular output line."
   INDEX { upsOutputLineIndex }
   ::= { upsOutputTable 1 }

UpsOutputEntry ::= SEQUENCE {

   upsOutputLineIndex   PositiveInteger,
   upsOutputVoltage     NonNegativeInteger,
   upsOutputCurrent     NonNegativeInteger,
   upsOutputPower       NonNegativeInteger,
   upsOutputPercentLoad INTEGER

}

upsOutputLineIndex OBJECT-TYPE

   SYNTAX     PositiveInteger
   MAX-ACCESS not-accessible
   STATUS     current
   DESCRIPTION
           "The output line identifier."
   ::= { upsOutputEntry 1 }

upsOutputVoltage OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "RMS Volts"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The present output voltage."
   ::= { upsOutputEntry 2 }

upsOutputCurrent OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "0.1 RMS Amp"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The present output current."
   ::= { upsOutputEntry 3 }

upsOutputPower OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "Watts"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The present output true power."
   ::= { upsOutputEntry 4 }

upsOutputPercentLoad OBJECT-TYPE

   SYNTAX     INTEGER (0..200)
   UNITS      "percent"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The percentage of the UPS power capacity presently
           being used on this output line, i.e., the greater of
           the percent load of true power capacity and the
           percent load of VA."
   ::= { upsOutputEntry 5 }

-- -- The Bypass group. --

upsBypass OBJECT IDENTIFIER ::= { upsObjects 5 }

upsBypassFrequency OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "0.1 Hertz"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The present bypass frequency."
   ::= { upsBypass 1 }

upsBypassNumLines OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The number of bypass lines utilized in this device.
           This entry indicates the number of rows in the bypass
           table."
   ::= { upsBypass 2 }

upsBypassTable OBJECT-TYPE

   SYNTAX     SEQUENCE OF UpsBypassEntry
   MAX-ACCESS not-accessible
   STATUS     current
   DESCRIPTION
           "A list of bypass table entries.  The number of
           entries is given by the value of upsBypassNumLines."
   ::= { upsBypass 3 }

upsBypassEntry OBJECT-TYPE

   SYNTAX     UpsBypassEntry
   MAX-ACCESS not-accessible
   STATUS     current
   DESCRIPTION
           "An entry containing information applicable to a
           particular bypass input."
   INDEX { upsBypassLineIndex }
   ::= { upsBypassTable 1 }

UpsBypassEntry ::= SEQUENCE {

   upsBypassLineIndex  PositiveInteger,
   upsBypassVoltage    NonNegativeInteger,
   upsBypassCurrent    NonNegativeInteger,
   upsBypassPower      NonNegativeInteger

}

upsBypassLineIndex OBJECT-TYPE

   SYNTAX     PositiveInteger
   MAX-ACCESS not-accessible
   STATUS     current
   DESCRIPTION
           "The bypass line identifier."
   ::= { upsBypassEntry 1 }

upsBypassVoltage OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "RMS Volts"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The present bypass voltage."
   ::= { upsBypassEntry 2 }

upsBypassCurrent OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "0.1 RMS Amp"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The present bypass current."
   ::= { upsBypassEntry 3 }

upsBypassPower OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "Watts"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The present true power conveyed by the bypass."
   ::= { upsBypassEntry 4 }

-- -- The Alarm group. --

upsAlarm OBJECT IDENTIFIER ::= { upsObjects 6 }

upsAlarmsPresent OBJECT-TYPE

   SYNTAX     Gauge32
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The present number of active alarm conditions."
   ::= { upsAlarm 1 }

upsAlarmTable OBJECT-TYPE

   SYNTAX     SEQUENCE OF UpsAlarmEntry
   MAX-ACCESS not-accessible
   STATUS     current
   DESCRIPTION
           "A list of alarm table entries.  The table contains
           zero, one, or many rows at any moment, depending upon
           the number of alarm conditions in effect.  The table
           is initially empty at agent startup.  The agent
           creates a row in the table each time a condition is
           detected and deletes that row when that condition no
           longer pertains.  The agent creates the first row with
           upsAlarmId equal to 1, and increments the value of
           upsAlarmId each time a new row is created, wrapping to
           the first free value greater than or equal to 1 when
           the maximum value of upsAlarmId would otherwise be
           exceeded.  Consequently, after multiple operations,
           the table may become sparse, e.g., containing entries
           for rows 95, 100, 101, and 203 and the entries should
           not be assumed to be in chronological order because
           upsAlarmId might have wrapped.
           Alarms are named by an AutonomousType (OBJECT
           IDENTIFIER), upsAlarmDescr, to allow a single table to
           reflect well known alarms plus alarms defined by a
           particular implementation, i.e., as documented in the
           private enterprise MIB definition for the device.  No
           two rows will have the same value of upsAlarmDescr,
           since alarms define conditions.  In order to meet this
           requirement, care should be taken in the definition of
           alarm conditions to insure that a system cannot enter
           the same condition multiple times simultaneously.
           The number of rows in the table at any given time is
           reflected by the value of upsAlarmsPresent."
   ::= { upsAlarm 2 }

upsAlarmEntry OBJECT-TYPE

   SYNTAX     UpsAlarmEntry
   MAX-ACCESS not-accessible
   STATUS     current
   DESCRIPTION
           "An entry containing information applicable to a
           particular alarm."
   INDEX { upsAlarmId }
   ::= { upsAlarmTable 1 }

UpsAlarmEntry ::= SEQUENCE {

   upsAlarmId          PositiveInteger,
   upsAlarmDescr       AutonomousType,
   upsAlarmTime        TimeStamp

}

upsAlarmId OBJECT-TYPE

   SYNTAX     PositiveInteger
   MAX-ACCESS not-accessible
   STATUS     current
   DESCRIPTION
           "A unique identifier for an alarm condition.  This
           value must remain constant."
   ::= { upsAlarmEntry 1 }

upsAlarmDescr OBJECT-TYPE

   SYNTAX     AutonomousType
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "A reference to an alarm description object.  The
           object referenced should not be accessible, but rather
           be used to provide a unique description of the alarm
           condition."
   ::= { upsAlarmEntry 2 }

upsAlarmTime OBJECT-TYPE

   SYNTAX     TimeStamp
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The value of sysUpTime when the alarm condition was
           detected.  If the alarm condition was detected at the
           time of agent startup and presumably existed before
           agent startup, the value of upsAlarmTime shall equal
           0."
   ::= { upsAlarmEntry 3 }

-- -- Well known alarm conditions. --

upsWellKnownAlarms OBJECT IDENTIFIER ::= { upsAlarm 3 }

upsAlarmBatteryBad OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "One or more batteries have been determined to require
           replacement."
   ::= { upsWellKnownAlarms  1 }

upsAlarmOnBattery OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The UPS is drawing power from the batteries."
   ::= { upsWellKnownAlarms  2 }

upsAlarmLowBattery OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The remaining battery run-time is less than or equal
           to upsConfigLowBattTime."
   ::= { upsWellKnownAlarms  3 }

upsAlarmDepletedBattery OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The UPS will be unable to sustain the present load
           when and if the utility power is lost."
   ::= { upsWellKnownAlarms  4 }

upsAlarmTempBad OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "A temperature is out of tolerance."
   ::= { upsWellKnownAlarms  5 }

upsAlarmInputBad OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "An input condition is out of tolerance."
   ::= { upsWellKnownAlarms  6 }

upsAlarmOutputBad OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "An output condition (other than OutputOverload) is
           out of tolerance."
   ::= { upsWellKnownAlarms  7 }

upsAlarmOutputOverload OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The output load exceeds the UPS output capacity."
   ::= { upsWellKnownAlarms  8 }

upsAlarmOnBypass OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The Bypass is presently engaged on the UPS."
   ::= { upsWellKnownAlarms  9 }

upsAlarmBypassBad OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The Bypass is out of tolerance."
   ::= { upsWellKnownAlarms 10 }

upsAlarmOutputOffAsRequested OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The UPS has shutdown as requested, i.e., the output
           is off."
   ::= { upsWellKnownAlarms 11 }

upsAlarmUpsOffAsRequested OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The entire UPS has shutdown as commanded."
   ::= { upsWellKnownAlarms 12 }

upsAlarmChargerFailed OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "An uncorrected problem has been detected within the
           UPS charger subsystem."
   ::= { upsWellKnownAlarms 13 }

upsAlarmUpsOutputOff OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The output of the UPS is in the off state."
   ::= { upsWellKnownAlarms 14 }

upsAlarmUpsSystemOff OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The UPS system is in the off state."
   ::= { upsWellKnownAlarms 15 }

upsAlarmFanFailure OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The failure of one or more fans in the UPS has been
           detected."
   ::= { upsWellKnownAlarms 16 }

upsAlarmFuseFailure OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The failure of one or more fuses has been detected."
   ::= { upsWellKnownAlarms 17 }

upsAlarmGeneralFault OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "A general fault in the UPS has been detected."
   ::= { upsWellKnownAlarms 18 }

upsAlarmDiagnosticTestFailed OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The result of the last diagnostic test indicates a
           failure."
   ::= { upsWellKnownAlarms 19 }

upsAlarmCommunicationsLost OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "A problem has been encountered in the communications
           between the agent and the UPS."
   ::= { upsWellKnownAlarms 20 }

upsAlarmAwaitingPower OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The UPS output is off and the UPS is awaiting the
           return of input power."
   ::= { upsWellKnownAlarms 21 }

upsAlarmShutdownPending OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "A upsShutdownAfterDelay countdown is underway."
   ::= { upsWellKnownAlarms 22 }

upsAlarmShutdownImminent OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The UPS will turn off power to the load in less than
           5 seconds; this may be either a timed shutdown or a
           low battery shutdown."
   ::= { upsWellKnownAlarms 23 }

upsAlarmTestInProgress OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "A test is in progress, as initiated and indicated by
           the Test Group.  Tests initiated via other
           implementation-specific mechanisms can indicate the
           presence of the testing in the alarm table, if
           desired, via a OBJECT-IDENTITY macro in the MIB
           document specific to that implementation and are
           outside the scope of this OBJECT-IDENTITY."
   ::= { upsWellKnownAlarms 24 }

-- -- The Test Group --

upsTest OBJECT IDENTIFIER ::= { upsObjects 7 }

upsTestId OBJECT-TYPE

   SYNTAX     OBJECT IDENTIFIER
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "The test is named by an OBJECT IDENTIFIER which
           allows a standard mechanism for the initiation of
           tests, including the well known tests identified in
           this document as well as those introduced by a
           particular implementation, i.e., as documented in the
           private enterprise MIB definition for the device.
           Setting this variable initiates the named test. Sets
           to this variable require the presence of
           upsTestSpinLock in the same SNMP message.
           The set request will be rejected with an appropriate
           error message if the requested test cannot be
           performed, including attempts to start a test when
           another test is already in progress.  The status of
           the current or last test is maintained in
           upsTestResultsSummary. Tests in progress may be
           aborted by setting the upsTestId variable to
           upsTestAbortTestInProgress.
           Read operations return the value of the name of the
           test in progress if a test is in progress or the name
           of the last test performed if no test is in progress,
           unless no test has been run, in which case the well
           known value upsTestNoTestsInitiated is returned."
   ::= { upsTest 1 }

-- see [6] for more information on the semantics of objects with -- syntax of TestAndIncr

upsTestSpinLock OBJECT-TYPE

   SYNTAX     TestAndIncr
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "A spin lock on the test subsystem.  The spinlock is
           used as follows.
           Before starting a test, a manager-station should make
           sure that a test is not in progress as follows:
               try_again:
                 get (upsTestSpinLock)
                 while (upsTestResultsSummary == inProgress) {
                   /* loop while a test is running for another
           manager */
                   short delay
                   get (upsTestSpinLock)
                 }
                 lock_value = upsTestSpinLock
                 /* no test in progress, start the test */
                 set (upsTestSpinLock = lock_value, upsTestId =
           requested_test)
                 if (error_index == 1) { /* (upsTestSpinLock
           failed) */
                   /* if problem is not access control, then
                       some other manager slipped in ahead of us
           */
                   goto try_again
                 }
                 if (error_index == 2) { /* (upsTestId) */
                   /* cannot perform the test */
                   give up
                 }
                 /* test started ok */
                 /* wait for test completion by polling
           upsTestResultsSummary */
                 get (upsTestSpinLock, upsTestResultsSummary,
           upsTestResultsDetail)
                 while (upsTestResultsSummary == inProgress) {
                   short delay
                   get (upsTestSpinLock, upsTestResultsSummary,
           upsTestResultsDetail)
                 }
                 /* when test completes, retrieve any additional
           test results */
                 /* if upsTestSpinLock == lock_value + 1, then
           these are our test */
                 /* results (as opposed to another manager's */
                 The initial value of upsTestSpinLock at agent
           initialization shall
                 be 1."
   ::= { upsTest 2 }

upsTestResultsSummary OBJECT-TYPE

   SYNTAX     INTEGER {
       donePass(1),
       doneWarning(2),
       doneError(3),
       aborted(4),
       inProgress(5),
       noTestsInitiated(6)
   }
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The results of the current or last UPS diagnostics
           test performed.  The values for donePass(1),
           doneWarning(2), and doneError(3) indicate that the
           test completed either successfully, with a warning, or
           with an error, respectively.  The value aborted(4) is
           returned for tests which are aborted by setting the
           value of upsTestId to upsTestAbortTestInProgress.
           Tests which have not yet concluded are indicated by
           inProgress(5).  The value noTestsInitiated(6)
           indicates that no previous test results are available,
           such as is the case when no tests have been run since
           the last reinitialization of the network management
           subsystem and the system has no provision for non-
           volatile storage of test results."
   ::= { upsTest 3 }

upsTestResultsDetail OBJECT-TYPE

   SYNTAX     DisplayString (SIZE (0..255))
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "Additional information about upsTestResultsSummary.
           If no additional information available, a zero length
           string is returned."
   ::= { upsTest 4 }

upsTestStartTime OBJECT-TYPE

   SYNTAX     TimeStamp
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The value of sysUpTime at the time the test in
           progress was initiated, or, if no test is in progress,
           the time the previous test was initiated.  If the
           value of upsTestResultsSummary is noTestsInitiated(6),
           upsTestStartTime has the value 0."
   ::= { upsTest 5 }

upsTestElapsedTime OBJECT-TYPE

   SYNTAX     TimeInterval
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The amount of time, in TimeTicks, since the test in
           progress was initiated, or, if no test is in progress,
           the previous test took to complete.  If the value of
           upsTestResultsSummary is noTestsInitiated(6),
           upsTestElapsedTime has the value 0."
   ::= { upsTest 6 }

-- -- Well known tests. --

upsWellKnownTests OBJECT IDENTIFIER ::= { upsTest 7 }

upsTestNoTestsInitiated OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "No tests have been initiated and no test is in
           progress."
   ::= { upsWellKnownTests  1 }

upsTestAbortTestInProgress OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The test in progress is to be aborted / the test in
           progress was aborted."
   ::= { upsWellKnownTests  2 }

upsTestGeneralSystemsTest OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The manufacturer's standard test of UPS device
           systems."
   ::= { upsWellKnownTests  3 }

upsTestQuickBatteryTest OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "A test that is sufficient to determine if the battery
           needs replacement."
   ::= { upsWellKnownTests  4 }

upsTestDeepBatteryCalibration OBJECT-IDENTITY

   STATUS     current
   DESCRIPTION
           "The system is placed on battery to a discharge level,
           set by the manufacturer, sufficient to determine
           battery replacement and battery run-time with a high
           degree of confidence.  WARNING:  this test will leave
           the battery in a low charge state and will require
           time for recharging to a level sufficient to provide
           normal battery duration for the protected load."
   ::= { upsWellKnownTests  5 }

-- -- The Control group. --

upsControl OBJECT IDENTIFIER ::= { upsObjects 8 }

upsShutdownType OBJECT-TYPE

   SYNTAX     INTEGER {
       output(1),
       system(2)
   }
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "This object determines the nature of the action to be
           taken at the time when the countdown of the
           upsShutdownAfterDelay and upsRebootWithDuration
           objects reaches zero.
           Setting this object to output(1) indicates that
           shutdown requests should cause only the output of the
           UPS to turn off.  Setting this object to system(2)
           indicates that shutdown requests will cause the entire
           UPS system to turn off."
   ::= { upsControl 1 }

upsShutdownAfterDelay OBJECT-TYPE

   SYNTAX     INTEGER (-1..2147483648)
   UNITS      "seconds"
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "Setting this object will shutdown (i.e., turn off)
           either the UPS output or the UPS system (as determined
           by the value of upsShutdownType at the time of
           shutdown) after the indicated number of seconds, or
           less if the UPS batteries become depleted. Setting
           this object to 0 will cause the shutdown to occur
           immediately.  Setting this object to -1 will abort the
           countdown.  If the system is already in the desired
           state at the time the countdown reaches 0, then
           nothing will happen.  That is, there is no additional
           action at that time if upsShutdownType = system and
           the system is already off.  Similarly, there is no
           additional action at that time if upsShutdownType =
           output and the output is already off.  When read,
           upsShutdownAfterDelay will return the number of
           seconds remaining until shutdown, or -1 if no shutdown
           countdown is in effect.  On some systems, if the agent
           is restarted while a shutdown countdown is in effect,
           the countdown may be aborted.  Sets to this object
           override any upsShutdownAfterDelay already in effect."
   ::= { upsControl 2 }

upsStartupAfterDelay OBJECT-TYPE

   SYNTAX     INTEGER (-1..2147483648)
   UNITS      "seconds"
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "Setting this object will start the output after the
           indicated number of seconds, including starting the
           UPS, if necessary.  Setting this object to 0 will
           cause the startup to occur immediately.  Setting this
           object to -1 will abort the countdown.  If the output
           is already on at the time the countdown reaches 0,
           then nothing will happen.  Sets to this object
           override the effect of any upsStartupAfterDelay
           countdown or upsRebootWithDuration countdown in
           progress.  When read, upsStartupAfterDelay will return
           the number of seconds until startup, or -1 if no
           startup countdown is in effect.  If the countdown
           expires during a utility failure, the startup shall
           not occur until the utility power is restored.  On
           some systems, if the agent is restarted while a
           startup countdown is in effect, the countdown is
           aborted."
   ::= { upsControl 3 }

upsRebootWithDuration OBJECT-TYPE

   SYNTAX     INTEGER (-1..300)
   UNITS      "seconds"
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "Setting this object will immediately shutdown (i.e.,
           turn off) either the UPS output or the UPS system (as
           determined by the value of upsShutdownType at the time
           of shutdown) for a period equal to the indicated
           number of seconds, after which time the output will be
           started, including starting the UPS, if necessary.  If
           the number of seconds required to perform the request
           is greater than the requested duration, then the
           requested shutdown and startup cycle shall be
           performed in the minimum time possible, but in no case
           shall this require more than the requested duration
           plus 60 seconds.  When read, upsRebootWithDuration
           shall return the number of seconds remaining in the
           countdown, or -1 if no countdown is in progress.  If
           the startup should occur during a utility failure, the
           startup shall not occur until the utility power is
           restored."
   ::= { upsControl 4 }

upsAutoRestart OBJECT-TYPE

   SYNTAX     INTEGER {
       on(1),
       off(2)
   }
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "Setting this object to 'on' will cause the UPS system
           to restart after a shutdown if the shutdown occurred
           during a power loss as a result of either a
           upsShutdownAfterDelay or an internal battery depleted
           condition.  Setting this object to 'off' will prevent
           the UPS system from restarting after a shutdown until
           an operator manually or remotely explicitly restarts
           it.  If the UPS is in a startup or reboot countdown,
           then the UPS will not restart until that delay has
           been satisfied."
   ::= { upsControl 5 }

-- -- The Configuration group. --

upsConfig OBJECT IDENTIFIER ::= { upsObjects 9 }

upsConfigInputVoltage OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "RMS Volts"
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "The magnitude of the nominal input voltage.  On those
           systems which support read-write access to this
           object, if there is an attempt to set this variable to
           a value that is not supported, the request must be
           rejected and the agent shall respond with an
           appropriate error message, i.e., badValue for SNMPv1,
           or inconsistentValue for SNMPv2."
   ::= { upsConfig 1 }

upsConfigInputFreq OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "0.1 Hertz"
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "The nominal input frequency.  On those systems which
           support read-write access to this object, if there is
           an attempt to set this variable to a value that is not
           supported, the request must be rejected and the agent
           shall respond with an appropriate error message, i.e.,
           badValue for SNMPv1, or inconsistentValue for SNMPv2."
   ::= { upsConfig 2 }

upsConfigOutputVoltage OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "RMS Volts"
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "The magnitude of the nominal output voltage.  On
           those systems which support read-write access to this
           object, if there is an attempt to set this variable to
           a value that is not supported, the request must be
           rejected and the agent shall respond with an
           appropriate error message, i.e., badValue for SNMPv1,
           or inconsistentValue for SNMPv2."
   ::= { upsConfig 3 }

upsConfigOutputFreq OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "0.1 Hertz"
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "The nominal output frequency.  On those systems which
           support read-write access to this object, if there is
           an attempt to set this variable to a value that is not
           supported, the request must be rejected and the agent
           shall respond with an appropriate error message, i.e.,
           badValue for SNMPv1, or inconsistentValue for SNMPv2."
   ::= { upsConfig 4 }

upsConfigOutputVA OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "Volt-Amps"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The magnitude of the nominal Volt-Amp rating."
   ::= { upsConfig 5 }

upsConfigOutputPower OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "Watts"
   MAX-ACCESS read-only
   STATUS     current
   DESCRIPTION
           "The magnitude of the nominal true power rating."
   ::= { upsConfig 6 }

upsConfigLowBattTime OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "minutes"
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "The value of upsEstimatedMinutesRemaining at which a
           lowBattery condition is declared.  For agents which
           support only discrete (discontinuous) values, then the
           agent shall round up to the next supported value.  If
           the requested value is larger than the largest
           supported value, then the largest supported value
           shall be selected."
   ::= { upsConfig 7 }

upsConfigAudibleStatus OBJECT-TYPE

   SYNTAX     INTEGER {
       disabled(1),
       enabled(2),
       muted(3)
   }
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "The requested state of the audible alarm.  When in
           the disabled state, the audible alarm should never
           sound.  The enabled state is self-describing.  Setting
           this object to muted(3) when the audible alarm is
           sounding shall temporarily silence the alarm.  It will
           remain muted until it would normally stop sounding and
           the value returned for read operations during this
           period shall equal muted(3).  At the end of this
           period, the value shall revert to enabled(2).  Writes
           of the value muted(3) when the audible alarm is not
           sounding shall be accepted but otherwise shall have no
           effect."
   ::= { upsConfig 8 }

upsConfigLowVoltageTransferPoint OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "RMS Volts"
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "The minimum input line voltage allowed before the UPS
           system transfers to battery backup."
   ::= { upsConfig 9 }

upsConfigHighVoltageTransferPoint OBJECT-TYPE

   SYNTAX     NonNegativeInteger
   UNITS      "RMS Volts"
   MAX-ACCESS read-write
   STATUS     current
   DESCRIPTION
           "The maximum line voltage allowed before the UPS
           system transfers to battery backup."
   ::= { upsConfig 10 }

-- -- notifications, i.e., traps -- upsTraps OBJECT IDENTIFIER ::= { upsMIB 2 }

-- This section defines the well-known notifications sent by -- UPS agents. -- Care must be taken to insure that no particular notification -- is sent to a single receiving entity more often than once -- every five seconds.

upsTrapOnBattery NOTIFICATION-TYPE

   OBJECTS { upsEstimatedMinutesRemaining, upsSecondsOnBattery,
             upsConfigLowBattTime }
   STATUS  current
   DESCRIPTION
           "The UPS is operating on battery power.  This trap is
           persistent and is resent at one minute intervals until
           the UPS either turns off or is no longer running on
           battery."
 ::= { upsTraps 1 }

upsTrapTestCompleted NOTIFICATION-TYPE

   OBJECTS { upsTestId, upsTestSpinLock,
             upsTestResultsSummary, upsTestResultsDetail,
             upsTestStartTime, upsTestElapsedTime }
   STATUS  current
   DESCRIPTION
           "This trap is sent upon completion of a UPS diagnostic
           test."
 ::= { upsTraps 2 }

upsTrapAlarmEntryAdded NOTIFICATION-TYPE

   OBJECTS { upsAlarmId, upsAlarmDescr }
   STATUS  current
   DESCRIPTION
           "This trap is sent each time an alarm is inserted into
           to the alarm table.  It is sent on the insertion of
           all alarms except for upsAlarmOnBattery and
           upsAlarmTestInProgress."
 ::= { upsTraps 3 }

upsTrapAlarmEntryRemoved NOTIFICATION-TYPE

   OBJECTS { upsAlarmId, upsAlarmDescr }
   STATUS  current
   DESCRIPTION
           "This trap is sent each time an alarm is removed from
           the alarm table.  It is sent on the removal of all
           alarms except for upsAlarmTestInProgress."
 ::= { upsTraps 4 }

-- -- conformance information -- upsConformance OBJECT IDENTIFIER ::= { upsMIB 3 }

upsCompliances OBJECT IDENTIFIER ::= { upsConformance 1 }

-- -- compliance statements --

upsSubsetCompliance MODULE-COMPLIANCE

   STATUS     current
   DESCRIPTION
           "The compliance statement for UPSs that only support
           the two-contact communication protocol."
   MODULE -- this module
       MANDATORY-GROUPS  { upsSubsetIdentGroup,
                 upsSubsetBatteryGroup, upsSubsetInputGroup,
                 upsSubsetOutputGroup, upsSubsetAlarmGroup,
                 upsSubsetControlGroup, upsSubsetConfigGroup }
   OBJECT     upsBatteryStatus
   SYNTAX     INTEGER {
       batteryNormal(2),
       batteryLow(3)
   }
   DESCRIPTION
           "Support of the values unknown(1) and
           batteryDepleted(4) is not required."
   OBJECT     upsAlarmDescr
   DESCRIPTION
           "Support of all `well known' alarm types is not
           required.  The well known alarm types which must be
           supported are: upsAlarmOnBattery, upsAlarmLowBattery,
           upsAlarmInputBad, upsAlarmUpsOutputOff,
           upsAlarmUpsSystemOff, and upsAlarmTestInProgress."
   OBJECT     upsOutputSource
   SYNTAX     INTEGER {
       normal(2),
       battery(4)
   }
   DESCRIPTION
           "Support of the values other(1), none(2), bypass(4),
           booster(6) and reducer(7) is not required."
   OBJECT     upsShutdownType
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required, i.e., compliant
           systems need not support more than one shutdown type."
   OBJECT     upsAutoRestart
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required, i.e., compliant
           systems need not support more than one restart type."
   OBJECT     upsConfigInputVoltage
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required."
   OBJECT     upsConfigInputFreq
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required."
   OBJECT     upsConfigOutputVoltage
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required."
   OBJECT     upsConfigOutputFreq
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required."
   ::= { upsCompliances 1 }

upsBasicCompliance MODULE-COMPLIANCE

   STATUS     current
   DESCRIPTION
           "The compliance statement for UPSs that support
           full-featured functions, such as control."
   MODULE -- this module
       MANDATORY-GROUPS { upsBasicIdentGroup,
                 upsBasicBatteryGroup, upsBasicInputGroup,
                 upsBasicOutputGroup, upsBasicAlarmGroup,
                 upsBasicTestGroup, upsBasicControlGroup,
                 upsBasicConfigGroup }
   OBJECT     upsAlarmDescr
   DESCRIPTION
           "Support of all `well known' alarm types is not
           required.  The well known alarm types which must be
           supported are: upsAlarmOnBattery, upsAlarmLowBattery,
           upsAlarmDepletedBattery, upsAlarmTempBad,
           upsAlarmInputBad, upsAlarmOutputOverload,
           upsAlarmOnBypass, upsAlarmBypassBad,
           upsAlarmOutputOffAsRequested,
           upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff,
           upsAlarmUpsSystemOff, upsAlarmGeneralFault,
           upsAlarmDiagnosticTestFailed,
           upsAlarmCommunicationsLost, upsAlarmShutdownPending,
           and upsAlarmTestInProgress."
   OBJECT     upsTestId
   DESCRIPTION
           "Support of all `well known' test types is not
           required.  If no tests are supported, then the only
           well known test type which must be supported is
           upsTestNoTestsInitiated."
   OBJECT     upsOutputSource
   SYNTAX     INTEGER {
       normal(2),
       battery(4)
   }
   DESCRIPTION
           "Support of the values other(1), none(2), bypass(4),
           booster(6) and reducer(7) is not required."
       GROUP upsBasicBypassGroup
       DESCRIPTION
           "The upsBasicBypassGroup is only required for UPSs
           that have a Bypass present."
   OBJECT     upsShutdownType
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required, i.e., compliant
           systems need not support more than one shutdown type."
   OBJECT     upsAutoRestart
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required, i.e., compliant
           systems need not support more than one restart type."
   OBJECT     upsConfigInputVoltage
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required."
   OBJECT     upsConfigInputFreq
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required."
   OBJECT     upsConfigOutputVoltage
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required."
   OBJECT     upsConfigOutputFreq
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required."
   OBJECT     upsConfigLowBattTime
   DESCRIPTION
           "Implementation of all possible values may be onerous
           for some systems.  Consequently, not all possible
           values must be supported.  However, at least two
           different manufacturer-selected values must be
           supported."
   ::= { upsCompliances 2 }

upsFullCompliance MODULE-COMPLIANCE

   STATUS     current
   DESCRIPTION
           "The compliance statement for UPSs that support
           advanced full-featured functions."
   MODULE -- this module
       MANDATORY-GROUPS { upsFullIdentGroup, upsFullBatteryGroup,
                 upsFullInputGroup, upsFullOutputGroup,
                 upsFullAlarmGroup, upsFullTestGroup,
                 upsFullControlGroup, upsFullConfigGroup }
   OBJECT     upsAlarmDescr
   DESCRIPTION
           "Support of all `well known' alarm types is not
           required.  The well known alarm types which must be
           supported are: upsAlarmBatteryBad, upsAlarmOnBattery,
           upsAlarmLowBattery, upsAlarmDepletedBattery,
           upsAlarmTempBad, upsAlarmInputBad, upsAlarmOnBypass,
           upsAlarmBypassBad, upsAlarmOutputOffAsRequested,
           upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff,
           upsAlarmUpsSystemOff, upsAlarmGeneralFault,
           upsAlarmDiagnosticTestFailed,
           upsAlarmCommunicationsLost, upsAlarmShutdownPending,
           and upsAlarmTestInProgress."
   OBJECT     upsTestId
   DESCRIPTION
           "Support of all `well known' test types is not
           required.  The well known test types which must be
           supported are: upsTestNoTestsInitiated,
           upsTestGeneralSystemsTest, and
           upsTestQuickBatteryTest."
   OBJECT     upsOutputSource
   SYNTAX     INTEGER {
       normal(2),
       battery(4)
   }
   DESCRIPTION
           "Support of the values other(1), none(2), bypass(4),
           booster(6) and reducer(7) is not required."
       GROUP upsFullBypassGroup
       DESCRIPTION
           "The upsFullBypassGroup is only required for UPSs that
           have a Bypass present."
   OBJECT     upsShutdownType
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required, i.e., compliant
           systems need not support more than one shutdown type."
   OBJECT     upsAutoRestart
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required, i.e., compliant
           systems need not support more than one restart type."
   OBJECT     upsConfigInputVoltage
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required."
   OBJECT     upsConfigInputFreq
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required."
   OBJECT     upsConfigOutputVoltage
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required."
   OBJECT     upsConfigOutputFreq
   MIN-ACCESS read-only
   DESCRIPTION
           "Read-write access is not required."
   OBJECT     upsConfigLowBattTime
   DESCRIPTION
           "Implementation of all possible values may be onerous
           for some systems.  Consequently, not all possible
           values must be supported.  However, at least two
           different manufacturer-selected values must be
           supported."
   ::= { upsCompliances 3 }

-- -- units of conformance --

-- summary at a glance:

-- subset basic adv --upsIdentManufacturer x x x --upsIdentModel x x x

--upsIdentUPSSoftwareVersion x x --upsIdentAgentSoftwareVersion x x x --upsIdentName x x x --upsIdentAttachedDevices x x -- --upsBatteryStatus x x x notes --upsSecondsOnBattery x x x --upsEstimatedMinutesRemaining x --upsEstimatedChargeRemaining x --upsBatteryVoltage --upsBatteryCurrent --upsBatteryTemperature -- --upsInputLineBads x x x --upsInputNumLines x x --upsInputFrequency x x --upsInputVoltage x x --upsInputCurrent --upsInputTruePower -- --upsOutputSource x x x notes --upsOutputFrequency x x --upsOutputNumLines x x --upsOutputVoltage x x --upsOutputCurrent x --upsOutputPower x --upsOutputPercentLoad x -- -- --upsBypassFrequency x x notes --upsBypassNumLines x x --upsBypassVoltage x x --upsBypassCurrent --upsBypassPower -- -- --upsAlarmsPresent x x x --upsAlarmDescr x x x notes --upsAlarmTime x x x -- --upsTestId x x notes --upsTestSpinLock x x --upsTestResultsSummary x x --upsTestResultsDetail x x --upsTestStartTime x x --upsTestElapsedTime x x -- --upsShutdownType x x x notes

--upsShutdownAfterDelay x x x --upsStartupAfterDelay x x --upsRebootWithDuration x x --upsAutoRestart x x x notes -- --upsConfigInputVoltage x x x notes --upsConfigInputFreq x x x notes --upsConfigOutputVoltage x x x notes --upsConfigOutputFreq x x x notes --upsConfigOutputVA x x x --upsConfigOutputPower x x x --upsConfigLowBattTime x x notes --upsConfigAudibleStatus x x --upsConfigLowVoltageTransferPoint --upsConfigHighVoltageTransferPoint

-- units of conformance upsGroups OBJECT IDENTIFIER ::= { upsConformance 2 }

upsSubsetGroups OBJECT IDENTIFIER ::= { upsGroups 1 }

upsSubsetIdentGroup OBJECT-GROUP

   OBJECTS { upsIdentManufacturer, upsIdentModel,
             upsIdentAgentSoftwareVersion, upsIdentName,
             upsIdentAttachedDevices }
   STATUS  current
   DESCRIPTION
           "The upsSubsetIdentGroup defines objects which are
           common across all UPSs which meet subset compliance.
           Most devices which conform to the upsSubsetIdentGroup
           will provide access to these objects via a proxy
           agent.  If the proxy agent is compatible with multiple
           UPS types, configuration of the proxy agent will
           require specifying some of these values, either
           individually, or as a group (perhaps through a table
           lookup mechanism based on the UPS model number)."
   ::= { upsSubsetGroups 1 }

upsSubsetBatteryGroup OBJECT-GROUP

   OBJECTS { upsBatteryStatus, upsSecondsOnBattery }
   STATUS  current
   DESCRIPTION
           "The upsSubsetBatteryGroup defines the objects that
           are common to battery groups of two-contact UPSs."
   ::= { upsSubsetGroups 2 }

upsSubsetInputGroup OBJECT-GROUP

   OBJECTS { upsInputLineBads }
   STATUS  current
   DESCRIPTION
           "The upsSubsetInputGroup defines the objects that are
           common to the Input groups of two-contact UPSs."
   ::= { upsSubsetGroups 3 }

upsSubsetOutputGroup OBJECT-GROUP

   OBJECTS { upsOutputSource }
   STATUS  current
   DESCRIPTION
           "The upsSubsetOutputGroup defines the objects that are
           common to the Output groups of two-contact UPSs."
   ::= { upsSubsetGroups 4 }

-- { upsSubsetGroups 5 } is reserved for -- future use (upsSubsetBypassGroup)

upsSubsetAlarmGroup OBJECT-GROUP

   OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
   STATUS  current
   DESCRIPTION
           "The upsSubsetAlarmGroup defines the objects that are
           common to the Alarm groups of two-contact UPSs."
   ::= { upsSubsetGroups 6 }

-- { upsSubsetGroups 7 } is reserved for -- future use (upsSubsetTestGroup)

upsSubsetControlGroup OBJECT-GROUP

   OBJECTS { upsShutdownType, upsShutdownAfterDelay,
                 upsAutoRestart }
   STATUS  current
   DESCRIPTION
           "The upsSubsetControlGroup defines the objects that
           are common to the Control groups of two-contact UPSs."
   ::= { upsSubsetGroups 8 }

upsSubsetConfigGroup OBJECT-GROUP

   OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
             upsConfigOutputVoltage, upsConfigOutputFreq,
             upsConfigOutputVA, upsConfigOutputPower }
   STATUS  current
   DESCRIPTION
           "The upsSubsetConfigGroup defines the objects that are
           common to the Config groups of two-contact UPSs."
   ::= { upsSubsetGroups 9 }

upsBasicGroups OBJECT IDENTIFIER ::= { upsGroups 2 }

upsBasicIdentGroup OBJECT-GROUP

   OBJECTS { upsIdentManufacturer, upsIdentModel,
             upsIdentUPSSoftwareVersion,
             upsIdentAgentSoftwareVersion, upsIdentName }
   STATUS  current
   DESCRIPTION
           "The upsBasicIdentGroup defines objects which are
           common to the Ident group of compliant UPSs which
           support basic functions."
   ::= { upsBasicGroups 1 }

upsBasicBatteryGroup OBJECT-GROUP

   OBJECTS { upsBatteryStatus, upsSecondsOnBattery }
   STATUS  current
   DESCRIPTION
           "The upsBasicBatteryGroup defines the objects that are
           common to the battery groups of compliant UPSs which
           support basic functions."
   ::= { upsBasicGroups 2 }

upsBasicInputGroup OBJECT-GROUP

   OBJECTS { upsInputLineBads, upsInputNumLines,
             upsInputFrequency, upsInputVoltage }
   STATUS  current
   DESCRIPTION
           "The upsBasicInputGroup defines the objects that are
           common to the Input groups of compliant UPSs which
           support basic functions."
   ::= { upsBasicGroups 3 }

upsBasicOutputGroup OBJECT-GROUP

   OBJECTS { upsOutputSource, upsOutputFrequency,
             upsOutputNumLines, upsOutputVoltage }
   STATUS  current
   DESCRIPTION
           "The upsBasicOutputGroup defines the objects that are
           common to the Output groups of compliant UPSs which
           support basic functions."
   ::= { upsBasicGroups 4 }

upsBasicBypassGroup OBJECT-GROUP

   OBJECTS { upsBypassFrequency, upsBypassNumLines,
             upsBypassVoltage }
   STATUS  current
   DESCRIPTION
           "The upsBasicBypassGroup defines the objects that are
           common to the Bypass groups of compliant UPSs which
           support basic functions."
   ::= { upsBasicGroups 5 }

upsBasicAlarmGroup OBJECT-GROUP

   OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
   STATUS  current
   DESCRIPTION
           "The upsBasicAlarmGroup defines the objects that are
           common to the Alarm  groups of compliant UPSs which
           support basic functions."
   ::= { upsBasicGroups 6 }

upsBasicTestGroup OBJECT-GROUP

   OBJECTS { upsTestId, upsTestSpinLock,
             upsTestResultsSummary, upsTestResultsDetail,
             upsTestStartTime, upsTestElapsedTime }
   STATUS  current
   DESCRIPTION
           "The upsBasicTestGroup defines the objects that are
           common to the Test groups of compliant UPSs which
           support basic functions."
   ::= { upsBasicGroups 7 }

upsBasicControlGroup OBJECT-GROUP

   OBJECTS { upsShutdownType, upsShutdownAfterDelay,
             upsStartupAfterDelay, upsRebootWithDuration,
             upsAutoRestart }
   STATUS  current
   DESCRIPTION
           "The upsBasicControlGroup defines the objects that are
           common to the Control groups of compliant UPSs which
           support basic functions."
   ::= { upsBasicGroups 8 }

upsBasicConfigGroup OBJECT-GROUP

   OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
             upsConfigOutputVoltage, upsConfigOutputFreq,
             upsConfigOutputVA, upsConfigOutputPower,
             upsConfigLowBattTime, upsConfigAudibleStatus }
   STATUS  current
   DESCRIPTION
           "The upsBasicConfigGroup defines the objects that are
           common to the Config groups of UPSs which support
           basic functions."
   ::= { upsBasicGroups 9 }

upsFullGroups OBJECT IDENTIFIER ::= { upsGroups 3 }

upsFullIdentGroup OBJECT-GROUP

   OBJECTS { upsIdentManufacturer, upsIdentModel,
             upsIdentUPSSoftwareVersion,
             upsIdentAgentSoftwareVersion, upsIdentName,
             upsIdentAttachedDevices }
   STATUS  current
   DESCRIPTION
           "The upsFullIdentGroup defines objects which are
           common to the Ident group of fully compliant UPSs."
   ::= { upsFullGroups 1 }

upsFullBatteryGroup OBJECT-GROUP

   OBJECTS { upsBatteryStatus, upsSecondsOnBattery,
             upsEstimatedMinutesRemaining,
             upsEstimatedChargeRemaining }
   STATUS  current
   DESCRIPTION
           "The upsFullBatteryGroup defines the objects that are
           common to the battery groups of fully compliant UPSs."
   ::= { upsFullGroups 2 }

upsFullInputGroup OBJECT-GROUP

   OBJECTS { upsInputLineBads, upsInputNumLines,
             upsInputFrequency, upsInputVoltage }
   STATUS  current
   DESCRIPTION
           "The upsFullInputGroup defines the objects that are
           common to the Input groups of fully compliant UPSs."
   ::= { upsFullGroups 3 }

upsFullOutputGroup OBJECT-GROUP

   OBJECTS { upsOutputSource, upsOutputFrequency,
             upsOutputNumLines, upsOutputVoltage,
             upsOutputCurrent, upsOutputPower,
             upsOutputPercentLoad }
   STATUS  current
   DESCRIPTION
           "The upsFullOutputGroup defines the objects that are
           common to the Output groups of fully compliant UPSs."
   ::= { upsFullGroups 4 }

upsFullBypassGroup OBJECT-GROUP

   OBJECTS { upsBypassFrequency, upsBypassNumLines,
             upsBypassVoltage }
   STATUS  current
   DESCRIPTION
           "The upsFullBypassGroup defines the objects that are
           common to the Bypass groups of fully compliant UPSs."
   ::= { upsFullGroups 5 }

upsFullAlarmGroup OBJECT-GROUP

   OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
   STATUS  current
   DESCRIPTION
           "The upsFullAlarmGroup defines the objects that are
           common to the Alarm  groups of fully compliant UPSs."
   ::= { upsFullGroups 6 }

upsFullTestGroup OBJECT-GROUP

   OBJECTS { upsTestId, upsTestSpinLock,
             upsTestResultsSummary, upsTestResultsDetail,
             upsTestStartTime, upsTestElapsedTime }
   STATUS  current
   DESCRIPTION
           "The upsFullTestGroup defines the objects that are
           common to the Test groups of fully compliant UPSs."
   ::= { upsFullGroups 7 }

upsFullControlGroup OBJECT-GROUP

   OBJECTS { upsShutdownType, upsShutdownAfterDelay,
             upsStartupAfterDelay, upsRebootWithDuration,
             upsAutoRestart }
   STATUS  current
   DESCRIPTION

"The upsFullControlGroup defines the objects that are common to the Control groups of fully compliant UPSs."

   ::= { upsFullGroups 8 }

upsFullConfigGroup OBJECT-GROUP

   OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
             upsConfigOutputVoltage, upsConfigOutputFreq,
             upsConfigOutputVA, upsConfigOutputPower,
             upsConfigLowBattTime, upsConfigAudibleStatus }
   STATUS  current
   DESCRIPTION
           "The upsFullConfigGroup defines the objects that are
           common to the Config groups of fully compliant UPSs."
   ::= { upsFullGroups 9 }

END

Acknowledgements

The UPS MIB represents the combined work of the IETF UPS MIB Working Group, with particular, substantial authorship contributions from:

       Mike Davison
       Fibercom, Inc.
       Ray Wasson
       Consultant
       Roger Draper
       Liebert Corporation
       Ken Key
       SNMP Research, Incorporated
       Pete Yoest
       American Power Conversion
       Doug Rademacher
       American Power Conversion
       Ron Pitt
       Network Security Systems, Inc
       Terry Zumwalt
       International Power Machines
       Lawren Markle
       Tripp Lite
       Bill Elliot
       ONEAC
       Tom Brennan
       Exide Electronics
       Brian Young
       Best Power Technology

References

[1] Case, J., Fedor, M., Schoffstall, M., and J. Davin, "Simple

   Network Management Protocol", STD 15, RFC 1157, SNMP Research,
   Inc., Performance Systems International, Performance Systems
   International, MIT Laboratory for Computer Science, May 1990.

[2] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser, "Protocol

   Operations for Version 2 of the Simple Network Management
   Protocol (SNMPv2)", RFC 1448, SNMP Research, Inc., Hughes LAN
   Systems, Dover Beach Consulting, Inc., Carnegie Mellon
   University, April 1993.

[3] McCloghrie, K., and M. Rose, Editors, "Management Information

   Base for Network Management of TCP/IP-based internets: MIB-II",
   STD 17, RFC 1213, Hughes LAN Systems, Performance Systems
   International, March 1991.

[4] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser, "Structure

   of Management Information for Version 2 of the Simple Network
   Management Protocol (SNMPv2)", RFC 1442, SNMP Research, Inc.,
   Hughes LAN Systems, Dover Beach Consulting, Inc., Carnegie Mellon
   University, April 1993.

[5] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser,

   "Conformance Statements for Version 2 of the Simple Network
   Management Protocol (SNMPv2)", RFC 1444, SNMP Research, Inc.,
   Hughes LAN Systems, Dover Beach Consulting, Inc., Carnegie Mellon
   University, April, 1993.

[6] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser, "Textual

   Conventions for Version 2 of the Simple Network Management
   Protocol (SNMPv2)", RFC 1443, SNMP Research, Inc., Hughes LAN
   Systems, Dover Beach Consulting, Inc., Carnegie Mellon
   University, April 1993.

Security Considerations

Security issues are not discussed in this memo.